Solar DC Cable Guide for Rooftop and Solar Pump Installers
What IS 17293 and the ISI mark require, how to size solar DC cable by current and voltage drop, and installation mistakes to avoid, with worked examples.
In this article
- Why Solar Cable Is Different From House Wire
- The Standard: IS 17293 and the ISI Mark
- Step 1: Check the Current
- Step 2: Check Voltage Drop
- Worked Example: Home Rooftop System
- Worked Example: Solar Pump With a Long Array Run
- Installation Mistakes to Avoid
- Elmeck Solar Cable
- Frequently Asked Questions
- References
Solar panels sit in the sun for 25 years or more. The cable that connects them to the inverter or pump controller has to survive the same heat, UV and rain while carrying direct current at several hundred volts. That is why solar installations use dedicated solar DC cable, not ordinary house wire.
This guide is for rooftop and solar pump installers. It covers what the Indian standard requires, how to choose the size, and the installation mistakes that waste energy or cause faults later. It is published by Elmeck Wires & Cables, which makes solar DC cable, so read it as a practical guide rather than an independent review. The system designer should confirm the final cable selection for every project.
Why Solar Cable Is Different From House Wire
- High DC voltage: modules in a string are connected in series, so the voltage adds up to several hundred volts DC. IS 17293 cables are rated for 1,500 V DC.
- Outdoor life: the cable lies on roofs and structures in direct sun. It needs a UV-resistant outer sheath over the insulation, not a single PVC layer.
- Tinned, fine-stranded copper: tinning protects the strands from corrosion outdoors, and fine strands keep the cable flexible for routing between panels.
- Single-core construction: each conductor has its own insulation and sheath, which keeps positive and negative separated along the whole run.
PVC house wire is designed for fixed wiring inside buildings and conduits. It is the right product for a home's AC circuits, but it is not made for the DC side of a solar array. If you need a refresher on the two kinds of current, see AC vs DC explained.
The Standard: IS 17293 and the ISI Mark
The Indian standard for solar cable is IS 17293:2020, Electric Cables for Photovoltaic Systems for Rated Voltage 1,500 V d.c. It is closely aligned with the international standard IEC 62930, which covers single-core cables with cross-linked insulation and sheath for the DC side of PV systems.
Compliance is not optional. The Solar DC Cable and Fire Survival Cable (Quality Control) Order, 2023 (S.O. 3807(E), dated 24 August 2023) requires solar DC cable to conform to IS 17293 and carry the BIS Standard Mark under a licence. The order came into force six months after it was published.
Before you buy, check:
- The sheath is printed with IS 17293, the size in sq mm and the ISI mark with the manufacturer's CM/L licence number
- The licence is valid: search the CM/L number in the BIS Care app or on the BIS website
- The conductor strands are tinned (silver-coloured), not bare red copper
- The supplier gives you a datasheet with current ratings and maximum conductor resistance for each size
Step 1: Check the Current
In a string, the modules are connected in series, so the current in the string cable is the current of one module. Find the module's short-circuit current (Isc) on its label or datasheet. International practice (IEC 60364-7-712) requires the string cable to carry at least 1.25 times the string Isc, because panels can produce more than their rated current on very bright days.
- One string, module Isc 14 A: the cable must carry at least 1.25 × 14 = 17.5 A
- Two strings combined in parallel before the cable run: 1.25 × 14 × 2 = 35 A
Compare that figure with the cable's rating for the way it will be installed (in free air, on a surface, or bunched with other cables), and reduce it for hot roofs and grouped cables as the system design requires. Elmeck publishes ratings for each installation method on its solar cable page. On a single rooftop string, current is rarely the limit. Voltage drop usually is.
Step 2: Check Voltage Drop
Every metre of cable turns a little of the panels' output into heat. On the DC side that loss is lost generation every sunny hour for the life of the system. Rooftop solar technical specifications, such as the one published by UPNEDA in Uttar Pradesh, ask for DC cable sizes that keep voltage drop below 2%. Check the specification for your own scheme, state or tender.
The calculation for a DC run:
- Voltage drop (V) = current (A) × 2 × one-way length (m) × resistance (Ω/km) ÷ 1,000
- Voltage drop (%) = voltage drop ÷ string voltage at maximum power (Vmp) × 100
- The 2 accounts for the positive and negative cables
Maximum conductor resistance at 20°C for Class 5 tinned copper, as listed in IS 8130 and on Elmeck's datasheet:
- 2.5 sq mm: 8.21 Ω/km
- 4 sq mm: 5.09 Ω/km
- 6 sq mm: 3.39 Ω/km
- 10 sq mm: 1.95 Ω/km
Copper's resistance rises by about 0.4% for every degree Celsius. On a hot roof the conductor runs well above 20°C, so the examples below use the resistance at 70°C, about 1.2 times the 20°C value. For more on the method, see our voltage drop calculation guide.
Worked Example: Home Rooftop System
Example values (use your own module datasheet): one string of 8 modules, each with Vmp 41 V, Imp 13 A and Isc 14 A. The string voltage is 8 × 41 = 328 V. The inverter is 25 m from the array, so there is 50 m of cable counting positive and negative.
- Current check: 1.25 × 14 = 17.5 A, well within the rating of 4 sq mm
- 2.5 sq mm: 6.39 V drop = 1.95%. Just inside 2%, with no margin for a longer run
- 4 sq mm: 3.96 V drop = 1.21%
- 6 sq mm: 2.64 V drop = 0.80%
4 sq mm is the sensible choice here. Move up to 6 sq mm if the run is longer or the string voltage is lower.
Worked Example: Solar Pump With a Long Array Run
Pump arrays are often placed away from the pump house to find shade-free ground, which makes the DC run long. Example values: two strings of 10 modules (Vmp 410 V, Imp 13 A, Isc 14 A per string) combined at the array junction box, so 26 A flows to the controller. The controller is 60 m away, so there is 120 m of cable.
- Current check: 1.25 × 14 × 2 = 35 A. 4 sq mm leaves little margin once derated, so start at 6 sq mm
- 6 sq mm: 12.66 V drop = 3.09%. Fails a 2% limit
- 10 sq mm: 7.28 V drop = 1.78%. Passes
- Alternative: run each string on its own pair of 6 sq mm cables and combine them near the controller. Each pair carries 13 A, giving about 1.5% drop
From the controller to the pump, including the length down the borewell, use submersible flat cable, not solar cable. That part of the run is sized for the pump motor's current and the borewell depth.
Installation Mistakes to Avoid
- Using PVC house wire or multi-core flexible cable on the DC side. Rooftop specifications ask for single-core cable there
- Mixing connector brands. Use matching connectors of the same type and make on both halves, crimped with the tool the connector maker specifies
- Leaving cable loose on the roof or over sharp structure edges. Route it in RPVC conduit or covered GI cable tray and clamp it at short intervals
- Running positive and negative far apart. Keep each pair together to keep the wiring loop small, which reduces voltages induced by nearby lightning
- Not labelling strings. Use red-lined cable or red markers for positive, and tag every string at both ends
- Sizing on current alone. On long runs, voltage drop decides the size
Elmeck Solar Cable
Elmeck Solar Cable is manufactured in accordance with IS 17293:2020, with a fine-stranded annealed tinned copper conductor, LSZH insulation and a UV-resistant outer sheath. It is available in 2.5, 4, 6 and 10 sq mm, in black and in black with red lining for easy polarity marking. Current ratings, dimensions and the datasheet are on the solar cables page.
Frequently Asked Questions
Can I use normal PVC house wire for solar panels?
No. Solar DC cable sold in India must conform to IS 17293 and carry the ISI mark under the Solar DC Cable and Fire Survival Cable (Quality Control) Order, 2023. PVC house wire is made for indoor fixed wiring, not for years of sun, heat and rain on a roof.
What size solar cable is used for a home rooftop system?
Many single-string home systems use 4 sq mm, but the right size depends on the string current and the cable length. Check that the cable carries at least 1.25 times the module short-circuit current and that voltage drop stays below the limit in your scheme's specification, often 2%.
Why is solar cable made with tinned copper?
The tin coating protects the fine copper strands from corrosion outdoors and in humid conditions. Fine strands also make the cable flexible enough to route neatly between panels.
Which cable goes down the borewell on a solar pump?
Solar DC cable runs from the panels to the pump controller. From the controller to the pump, including the length inside the borewell, use submersible flat cable made for that job.
References
- Bureau of Indian Standards, IS 17293:2020, Electric Cables for Photovoltaic Systems for Rated Voltage 1,500 V d.c.
- Gazette of India, S.O. 3807(E), 24 August 2023, Solar DC Cable and Fire Survival Cable (Quality Control) Order, 2023
- BSI, scope of IEC 62930, Electric cables for photovoltaic systems with a voltage rating of 1.5 kV DC
- UPNEDA, Technical specifications for rooftop solar plants installed under simplified procedure (cables section: voltage drop, single-core DC cable, routing)
- IS 8130, Conductors for insulated electric cables and flexible cords (Class 5 conductor resistance)
- IEC 60364-7-712, Solar photovoltaic (PV) power supply systems (string cable current rating)
Keep reading
Electrical Wiring Cost for a House in India — Full Breakdown by BHK & Material
Complete pricing guide for house electrical wiring by BHK, material type, and wire gauge. Calculate costs, labor, and material quantities with real examples.
Best House Wire in India: What Buyers Should Compare
A practical guide to comparing house-wire markings, construction, insulation, certification documents, and supplier support. Published by Elmeck Wires & Cables.
Short Circuit Current Rating of Cables — The Adiabatic Equation Explained
Undersized cables in high-fault-level installations can catch fire in milliseconds. Learn the adiabatic equation, worked examples for 10kA and 25kA systems, and coordination with protection devices.
Cable Sizing for Industrial Three-Phase Loads — Derating, Protection & Worked Examples
Residential cable sizing rules don't apply in industrial settings. Learn derating factors, how to handle motor starting currents, and protection coordination to IS 3961.