Submersible Cable Size Chart by Pump HP and Borewell Depth
Which flat cable size for a 0.5–20 HP borewell pump? A chart of maximum cable length by size, based on IS 9283 motor currents and 3% voltage drop.
In this article
A submersible pump can hang 100 metres or more down a borewell, with the starter in a pump house some distance away. Every metre of that cable carries the motor's full current and costs a little voltage. So the right cable size depends on two things: the pump's HP and how far the motor is from the starter. Choose by HP alone and a deep-set pump can end up running on low voltage.
This guide gives a size chart worked out from the Indian standard for submersible pump motors, IS 9283, and shows how to check your own installation. It is published by Elmeck Wires & Cables, which makes submersible cable, so read it as a practical guide. The pump supplier or installer should confirm the final selection.
Why Pump Depth Matters as Much as HP
Copper has resistance, so part of the supply voltage is lost along the cable before it reaches the motor. The longer the cable and the higher the current, the bigger the loss. IS 9283:2013 recommends choosing the conductor size and cable length so that the voltage drop between the control panel and the motor terminals is no more than 3% of the motor's rated voltage:
- Three-phase motor rated 415 V: no more than 12.45 V lost in the cable
- Single-phase motor rated 240 V: no more than 7.2 V
The standard also sets how much the voltage at the motor terminals may vary. Category A motors must work within ±6% of rated voltage. Category B motors must work from 6% above to 15% below it. The category is printed on the rating plate. Cable drop uses up part of that margin, and on a rural feeder where the supply is already low, it can push the motor outside it. Low voltage also means heat: in the standard's temperature test for Category B motors, the winding may rise up to 35°C at rated voltage but up to 45°C at 85% of rated voltage.
The Two Numbers You Need: Cable Length and Motor Current
Cable length is not the borewell depth. Add up:
- The depth at which the pump hangs, which is usually less than the full depth of the borewell
- The run from the top of the borewell to the starter or control panel
- A few metres for the joint, the connection at the panel and some slack
Under IS 9283 the motor comes with a lead of at least 2 m unless the buyer specifies the length, so the main cable is usually joined to it. The motor maker has to supply a watertight jointing procedure. Follow it exactly, because that joint spends its life under water.
Motor current is on the motor's rating plate, which IS 9283 requires to show the approximate current at rated output. If you don't have the plate, the standard's performance tables give the maximum full-load current allowed for each rating, and the chart below uses those maximum values. Pumps are sold by HP and motors are rated in kW: 1 HP is 0.746 kW, so a 5 HP pump has a 3.7 kW motor. Single-phase motors draw more current than three-phase motors of the same rating; see single phase vs three phase supply for why.
Submersible Cable Size Chart
Find your pump in the left column, then move right to the first size whose length is at least your cable length. Each figure is the longest cable run, in metres, that keeps voltage drop within 3%. Scroll the table sideways on a phone.
| PumpkW · max current | 1.5sq mm | 2.5sq mm | 4sq mm | 6sq mm | 10sq mm | 16sq mm | 25sq mm |
|---|---|---|---|---|---|---|---|
| 1.5 HP1.1 kW · 4.0 A | 110 | 185 | 300 | 450 | 500+ | 500+ | 500+ |
| 2 HP1.5 kW · 4.8 A | 90 | 155 | 250 | 375 | 500+ | 500+ | 500+ |
| 3 HP2.2 kW · 6.9 A | 65 | 105 | 175 | 260 | 450 | 500+ | 500+ |
| 4 HP3 kW · 9.0 A | under 60 m | 80 | 130 | 200 | 345 | 500+ | 500+ |
| 5 HP3.7 kW · 10.6 A | under 60 m | 70 | 110 | 170 | 295 | 465 | 500+ |
| 6 HP4.5 kW · 12.6 A | under 60 m | under 60 m | 95 | 140 | 245 | 390 | 500+ |
| 7.5 HP5.5 kW · 15.5 A | under 60 m | under 60 m | 75 | 115 | 200 | 315 | 495 |
| 10 HP7.5 kW · 19.5 A | under 60 m | under 60 m | 60 | 90 | 160 | 250 | 390 |
| 12.5 HP9.3 kW · 25.0 A | under 60 m | under 60 m | under 60 m | 70 | 125 | 195 | 305 |
| 15 HP11 kW · 29.0 A | under 60 m | under 60 m | under 60 m | 60 | 105 | 170 | 260 |
| 17.5 HP13 kW · 34.0 A | under 60 m | under 60 m | under 60 m | under 60 m | 90 | 145 | 225 |
| 20 HP15 kW · 39.0 A | under 60 m | under 60 m | under 60 m | under 60 m | 80 | 125 | 195 |
| PumpkW · max current | 2.5sq mm | 4sq mm | 6sq mm | 10sq mm | 16sq mm |
|---|---|---|---|---|---|
| 0.5 HP0.37 kW · 5.3 A | 70 | 110 | 170 | 295 | 465 |
| 0.75 HP0.55 kW · 6.2 A | 60 | 95 | 145 | 250 | 395 |
| 1 HP0.75 kW · 7.5 A | under 60 m | 80 | 120 | 205 | 330 |
| 1.5 HP1.1 kW · 10.5 A | under 60 m | under 60 m | 85 | 145 | 235 |
| 2 HP1.5 kW · 13.8 A | under 60 m | under 60 m | 65 | 110 | 175 |
How the chart was worked out:
- Current: the highest maximum full-load current IS 9283 allows for that rating (Tables 2 to 4 for three-phase water-filled motors in 100, 150 and 200 mm bores, Table 5 for single-phase water-filled motors)
- Three-phase voltage drop (V) = 1.732 × current (A) × cable length (m) × resistance (Ω/km) ÷ 1,000. For single-phase, use 2 in place of 1.732
- Resistance: the IS 8130 maximum for Class 5 flexible plain copper at 20°C (13.3, 7.98, 4.95, 3.30, 1.91, 1.21 and 0.780 Ω/km for 1.5 to 25 sq mm), multiplied by 1.2 for a conductor running at 70°C, the limit for general-purpose PVC cable. IS 8130 gives copper's resistance change as 0.004 per °C
- Lengths are rounded down to the nearest 5 m. A dash means the size allows less than 60 m; for a shorter run, use the formula and check the current rating
Cable hanging in borewell water usually runs cooler than 70°C, so the chart stays on the safe side. If your motor's rating plate shows a lower current than the chart, the allowed length rises in the same proportion. Whatever the length, the cable's current rating on its datasheet must be at least the motor's full-load current. Our voltage drop calculation guide explains the method in more detail.
Two Worked Examples
Farm borewell, 10 HP three-phase. Example values: the pump hangs at 150 m, the starter is 30 m from the borewell, and 5 m is added for the joint and connections, so the cable is 185 m long. The motor current is 19.5 A.
- Chart, 10 HP row: 10 sq mm allows 160 m, which is too short. 16 sq mm allows 250 m
- Check 16 sq mm: 1.732 × 19.5 × 185 × 1.452 ÷ 1,000 = 9.07 V, or 2.19%. Passes
- Check 10 sq mm: 14.32 V, or 3.45%. Above 3%
Home borewell, 1 HP single-phase. Example values: the pump hangs at 45 m, the control panel is 12 m from the borewell, and 3 m is added, so the cable is 60 m long. The motor current is 7.5 A.
- Chart, 1 HP row: 2.5 sq mm shows a dash (it allows about 50 m). 4 sq mm allows 80 m
- Check 4 sq mm: 2 × 7.5 × 60 × 5.94 ÷ 1,000 = 5.35 V, or 2.23%. Passes
- Check 2.5 sq mm: 8.62 V, or 3.59%. Above 3%
In both cases the cable length, not the HP alone, decided the size. If your area often has low supply voltage, a Category B motor and one cable size up give more margin.
Buying and Installation Checklist
- Buy cable made to IS 694, the standard IS 9283 refers to for the motor cable. IS 694:2010 covers PVC-insulated flat cables with two or three cores, and IS 694 cables are on BIS's list of products that cannot be sold without the ISI mark
- Check the markings: IS 694 requires the maker's name or trade mark on the sheath at least every metre, and a coil label showing IS 694, the conductor size, the number of cores and the year of manufacture
- Check the ISI mark carries a licence (CM/L) number, and look the number up in the BIS Care app
- With PVC column pipes, give the motor a separate earth path to the control panel. With four-core cable, the fourth core can be that earth
- Make the joint exactly as the motor maker's procedure says, then test insulation with a 500 V insulation tester before lowering the pump and again after jointing. Compare the reading with the motor maker's minimum
- Tie the cable to the delivery pipe at regular intervals, so its weight does not hang on the joint or the motor lead
Elmeck makes three submersible cable ranges: ResQFire+ and ResQFire for deep borewells and continuous full-load running, Alron for medium-depth residential and agricultural pumps, and Areek for standard-depth pumps with light to moderate duty. Ask for the datasheet of the size you need before you buy. On a solar pump, the cable from the panels to the controller is solar DC cable; see our solar DC cable guide.
Frequently Asked Questions
What size cable do I need for a 5 HP submersible pump?
It depends on the cable length. For a 5 HP three-phase motor, keeping voltage drop within 3% allows 2.5 sq mm up to about 70 m, 4 sq mm up to 110 m, 6 sq mm up to 170 m and 10 sq mm up to 295 m.
What size cable is used for a 1 HP single-phase borewell pump?
4 sq mm keeps voltage drop within 3% up to about 80 m, 6 sq mm up to 120 m and 10 sq mm up to 205 m. 2.5 sq mm stays within 3% only up to about 50 m.
Is the borewell depth the same as the cable length?
No. The cable runs from the starter or control panel to the motor: the depth at which the pump hangs, plus the run from the borewell to the panel, plus a few metres for the joint and connections. The pump usually hangs above the bottom of the borewell.
Why use four-core submersible cable?
When the column pipe is PVC, the pipe cannot carry the earth connection. IS 9283 calls for a separate earth path from the motor to the control panel in that case, and the fourth core of a four-core cable can be used as that earth.
References
- Bureau of Indian Standards, IS 9283:2013, Motors for Submersible Pumpsets — Specification (clause 5.1 motor cable and 3% voltage drop, 5.4 earthing with PVC pipes, 6.2 voltage categories, 15.1 rating plate, 19.1 temperature rise, 21 insulation resistance, Tables 2 to 5 maximum full-load current)
- Bureau of Indian Standards, IS 694:2010, PVC Insulated Unsheathed and Sheathed Cables/Cords with Rigid and Flexible Conductor (clause 11 and 15.2 marking, clause 22 flat cables, 70°C and 85°C conductor temperature)
- Bureau of Indian Standards, IS 8130, Conductors for Insulated Electric Cables and Flexible Cords (Table 3, Class 5 conductor resistance; Table 6 temperature correction)
- Bureau of Indian Standards, Products under compulsory certification (Scheme I): IS 694 PVC insulated cables under the Electrical Wires, Cables, Appliances and Protection Devices and Accessories (Quality Control) Order, 2003
Keep reading
Solar DC Cable Guide for Rooftop and Solar Pump Installers
What IS 17293 and the ISI mark require, how to size solar DC cable by current and voltage drop, and installation mistakes to avoid, with worked examples.
Electrical Wiring Cost for a House in India: Per Sq Ft and BHK-wise Breakdown
House wiring costs about ₹44–71 per sq ft in India. See totals for 1 to 4 BHK homes, how much wire a 1,000 sq ft house needs, and labour rates.
Best House Wire in India: What Buyers Should Compare
A practical guide to comparing house-wire markings, construction, insulation, certification documents, and supplier support. Published by Elmeck Wires & Cables.
Short Circuit Current Rating of Cables — The Adiabatic Equation Explained
Undersized cables in high-fault-level installations can catch fire in milliseconds. Learn the adiabatic equation, worked examples for 10kA and 25kA systems, and coordination with protection devices.